EasyManua.ls Logo

Siemens LOGO! Series - Technical Data: LOGO! 24 RC

Siemens LOGO! Series
534 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Technical data
A.6 Technical data: LOGO! 24RC...
LOGO!
330 Manual, 04/2011, A5E03556174-01
A.6 Technical data: LOGO! 24RC...
LOGO! 24RC
LOGO! 24RCo
Power supply
Input voltage 24 V AC/DC
Permissible range 20.4 ... 26.4 V AC
20.4 ... 28.8 V DC
Reverse polarity protection - -
Permissible mains frequency 47 ... 63 Hz
Power consumption
24 V AC
24 V DC
45 ... 130 mA
40 ... 100 mA
Voltage failure buffering typ. 5 ms
Power loss
24 V AC
24 V DC
1.1... 3.1 W
1.0 ... 2.4 W
Backup of the real-time clock at 25 °C typ. 80 hours without battery card
typ. 2 years with battery card
Accuracy of the real-time clock typ. ± 2 s / day
Digital inputs
Number 8,
optional P action or N action
Electrical isolation No
Number of high speed inputs 0
Input frequency
Normal input
High speed input
max. 4 Hz
- -
Max. continuous permissible voltage 26.4 V AC
28.8 V DC
Input voltage
Signal 0
Signal 1
L
< 5 V AC/DC
> 12 V AC/DC
Input current at
Signal 0
Signal 1
< 1.0 mA
> 2.5 mA
Delay time at
0 to 1
1 to 0
typ. 1.5 ms
typ. 15 ms
Line length (unshielded) max. 100 m
Analog inputs
Number - -

Table of Contents

Related product manuals