Configuring LOGO!
7.2 Setting the default values for LOGO!
LOGO!
Manual, 04/2011, A5E03556174-01
299
7.2.4 Setting the number of AIs in the LOGO! Basic
LOGO! 12/24RC/RCo/RCE, LOGO! 24/24o and LOGO! 24C/24Co support up to four
onboard inputs that can be used as either digital or analog inputs (0 ...10V). Inputs I7 (AI1)
and I8 (AI2) are available as analog inputs by default, whether you use them or not. Inputs I1
(AI3) and I2 (AI4) are optional analog inputs. A LOGO! Basic provides a menu where you
can choose to use two analog inputs (the default, AI1 and AI2), or four. Regardless of the
settings, inputs I1 and I2 can be used as digital inputs. To use them as analog inputs AI3
and AI4, you must set the 'BM AI NUM' to four. Note that the number of configured analog
inputs on the LOGO! Basic affects the subsequent numbering of analog inputs on attached
expansion modules (See the "
Maximum setup (Page 34)" topic).
You can set the number of AIs in programming mode only.
To set the number of AIs in programming mode:
1. In the main menu, select "": Press or
6WDUW
!6HWXS
&DUG
3URJUDP
2. Confirm "
": Press OK
%0$,180
0HQX/DQJ
/&'
!&ORFN
3. Select "
": Press or
4. Confirm "
": Press OK
5. Move to "2AI" or "4AI": Press
or
6. Confirm selection: Press O
K
Note
If you change the number of analog inputs, LOGO! restarts automatically.
See also
Selecting parameter assignment mode (Page 288)