LOGO! functions
4.4 Special functions list - SF
LOGO!
256 Manual, 04/2011, A5E03556174-01
4.4.30 PI controller
Short description
Proportional-action and integral-action controllers. You can use both types of controller
individually or combined.
Symbol in LOGO! Wiring Description
Input A/M Set the mode of the controller:
1: automatic mode
0: manual mode
Input R Use the input R to reset the output AQ. As long as
this input is set, the input A/M is disabled.
Output AQ is set to 0.
Input PV Analog value: process variable, influences the output
$ᇄ
$4
$0
5
39
3DU
Parameter SP: Set-value assignment
Range of values:
-10,000 to +20,000
KC: Gain
Range of values:
00.00 to 99.99
TI: Integral time
Range of values:
00:01 to 99:59 m
Dir: Action direction of the controller
Range of values:
+ or -
Mq: Value from AQ with manual mode
Range of values:
0 to 1000
Min: Minimum value for PV
Range of values:
-10,000 to +20,000
Max: Maximum value for PV
Range of values:
-10,000 to +20,000
A: Gain
Range of values:
±10.00
B: Offset
Range of values:
±10,000
p: Number of decimals
Range of values:
0, 1, 2, 3