EasyManua.ls Logo

Siemens LOGO! Series - Page 263

Siemens LOGO! Series
534 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
LOGO! functions
4.4 Special functions list - SF
LOGO!
Manual, 04/2011, A5E03556174-01
263
Examples with Timing Diagrams
The following examples show how the PWM instruction modulates a digital output signal
from the analog input value:
Example 1
Analog input value: 500 (range 0 ...1000)
Periodic time T: 4 seconds
The digital output of the PWM function is 2 seconds high, 2 seconds low, 2 seconds high, 2
seconds low and continues in that pattern as long as parameter "En" = high.
(Q
0D[ 
$[ 
0LQ 
4
VHF VHF VHF
VHF VHF
VHF
VHF
Example 2
Analog input value: 300 (range 0 ...1000)
Periodic time T: 10 seconds
The digital output of the PWM function is 3 seconds high, 7 seconds low, 3 seconds high, 7
seconds low and continues in that pattern as long as parameter "En" = high.
(Q
0D[ 
$[ 
0LQ 
4
VHF VHF
VHF VHF
Calculation rule
Q = 1, for (Ax - Min)/ (Max - Min) of time period T, when Min < Ax < Max
Q = 0, for PT - [ (Ax - Min) / (Max - Min) ] of periodic time T.
Note: Ax in this calculation refers to the actual value Ax as calculated using the Gain and
Offset.

Table of Contents