UDF (User-Defined Function) (0BA7 only)
LOGO!
282 Manual, 04/2011, A5E03556174-01
Editing elements to the outputs of a UDF block:
If LOGO! shows the following screen form as shown in step 10 above and you want to
change the element connected to "1" where "1" indicates the first output of the UDF block
U01 that is connected to Q1, follow these steps:
8
4
)
3DU
1. Press ESC to return to the menu as shown in step 5 above. Repeat steps 6 and 7.
LOGO! shows the following display:
84
4
2. When the cursor is below the Q in Q1, press
, or to select another element from
available lists, for example, M3. Press
to move the cursor to the left.
0
3. When the cursor appears in an underscore, press OK.
4. Press
or to select UDF and LOGO! shows the following display:
0
8')
5. Press OK. LOGO! provides you with available UDF blocks configured in LOGO!Soft
Comfort, in this example, U01.
6. Press
until LOGO! steps into the following screen form for the first UDF block U01:
8
0
)
3DU
You have changed the element connected to the first output of U01 from Q1 to M3.