7ML19985CN01 Milltronics SF 500 – INSTRUCTION MANUAL Page 17
mmmmm
Installation
Installing Optional Plug-in Boards
You can order the following optional plug-ins from Siemens Milltronics:
SmartLinx module
Enhances the existing SF 500 Communications System by providing an interface in one of
several popular industrial communications standards.
Analog Input / Output board
The mA I/O board provides 2 programmable 0/4-20 mA outputs, 2 programmable 0/4-20
mA inputs and a nominal 24V dc supply for loop-powered devices.
To Install a Plug-in Board
1. Turn off the power to the SF 500
2. Turn off any power provided to the relay contacts
3. Open the lid
4. Install the plug-in by mating the connectors
5. Secure it in place using the screws provided
6. For the SmartLinx® module only, route the communication cable along the right side
of the enclosure wall to reduce interference. Consult the SmartLinx®
documentation for any required hardware settings.
7. Close the lid
8. Restore power to the SF 500
mA I/O board
SmartLinx
®
route SmartLinx
®
cable
along right hand wall