Page 54 Milltronics SF 500 - INSTRUCTION MANUAL 7ML19985CN01
mmmmm
PID Control
Setpoint Controller – Rate Control
*Set to 1 for Remote Setpoint operation
Default Value =
f
Comments:
1. Connect signal to controlled device to mA O/P 2
2. For Remote Setpoint (optional). Connect remote 4-20 mA setpoint to I/P mA 1
Parameter Index Choices
01 02 03
Controller Selection P400- 1
0
f
---- 0=Off, 1=Man, 2=Auto
Process Variable Source P402-
1
f
1
f
----
1=Rate, 2=mA I/P 1,
3=mA I/P 2
Setpoint Configuration P414-
0
f*
0
f
----
0=Local, 1=mA I/P 1,
2=mA I/P 2
mA O/P Function P201-
1
f
2
1
f
1=Rate, 2=PID
mA I/P Function P255-
0
f*
0
f
----
0=Off, 1=PID Set-
point, 2=PID Process
Variable
ENTERCLEAR
RESET
TOT AL
ALT
DISP
RUN PAR ZERO SPAN
M
A
impact force
PID O/P demand rate
motor
speed
controller
optional remote setpoint
process variable (rate)
screw conveyor
Figure A