7ML19985CN01 Milltronics SF 500 - INSTRUCTION MANUAL Page 57
mmmmm
PID Control
SF 500 - Master
Default Value =
f
Comments:
1. Connect Rate output of SF 500-Master mA O/P 1, or mA O/P 3 to mA I/P 1 of
SF 500-Slave
Connect signal to controlled device from mA O/P 2
2. For Remote Setpoint on Rate Control (optional)
Connect remote 4-20 mA setpoint to mA I/P 1
Ratio of Primary product to remote setpoint may be adjusted by changing P418-01
SF 500 - Slave
Default Value =
f
Comments:
1. Connect primary rate controlled device to mA 2 O/P
2. Ratio of Additive to Primary product may be adjusted by changing P418-01
Parameter Index Choices
01 02 03
Controller Selection P400- 1
0
f
---- 0=Off, 1=Man, 2=Auto
Process Variable Source P402-
1
f
1
f
----
1=Rate, 2=mA I/P 1,
3=mA I/P 2
Setpoint Configuration P414-
0
f
0
f
----
0=Local, 1=mA I/P 1,
2=mA I/P 2
mA O/P Function P201-
1
f
2
1
f
1=Rate, 2=PID
mA I/P Function P255-
0
f
0
f
----
0=Off, 1=PID Set-
point, 2=PID Process
Variable
Remote Ratio (optional) P418-
100
f
100
f
---- Setpoint=% of input
Parameter Index Choices
01 02 03
Controller Selection P400- 1
0
f
---- 0=Off, 1=Man, 2=Auto
Process Variable Source P402-
1
f
1
f
----
1=Rate, 2=mA I/P 1,
3=mA I/P 2
Setpoint Configuration P414-
10
f
----
0=Local, 1=mA I/P 1,
2=mA I/P 2
mA O/P Function P201-
1
f
2
1
f
1=Rate, 2=PID
mA I/P Function P255-
10
f
----
0=Off, 1=PID Set-
point, 2=PID Process
Variable
Remote Ratio (optional) P418-
100
f
100
f
---- Setpoint=% of input