Page 106 Milltronics SF 500 - INSTRUCTION MANUAL 7ML19985CN01
mmmmm
Parameters
Linearization Parameters (P390 - P392)
These parameters are used to compensate for non-linear response of the weighing
system to the SF 500. Refer to
Linearization
on page 46 for execution, and example on the
use of these parameters.
P390 Linearizer
Enables or disables the linearization function.
Entry:
0 = OFF
f
1 = ON
P391 Linearizer Load Points
Enters the rate values, in units of P017, for the point selected, points 1 to 5 (P391-01 to
–05). (
f
= 0.00)
P392 Linearizer Compensation %
Enters the compensation value, in percent, for the point selected, point 1 to 5 (P392-01 to
– 05). (
f
= 0.00)
P398 Moisture Content
Factors out moisture component of rate and total for all multispans selected. The
factored values are meant to report the dry mean values of the material being conveyed.
(
f
= 0.00)
Enter the moisture content in % weight.
Proportional Integral Derivative (PID) Control
Parameters (P400 – P419)
Note: In the case of multispan operation, the linearizer is applied to all
spans.
Note:
Changes to P401, P402, and P414 are not immediately effected while in
auto mode. Change should be made in the manual mode and are
effected upon return to the auto mode.
The PID function does not control during any of the calibration functions
(e.g. zero, span, factor, material test).