Page 120 Milltronics SF 500 - INSTRUCTION MANUAL 7ML19985CN01
mmmmm
Troubleshooting
Error Codes
Error
Code
Code Name Message/Action
201 Error - Load Cell A & B
Reading between A & B > 20000, or no signal. Check
wiring.
203 Err: 203 Memory failure test. Consult Siemens Milltronics.
204 Integrator not configured P002-P017 must be programmed.
205 Err: 205 Zero or span calibration required.
210
Remote Totalizer 1
exceeded
Increase resolution.
211
Remote Totalizer 2
exceeded
Increase resolution.
213 Maximum rate exceeded
Rate is > thee times the design rate. If no mechanical
cause, check to see if re-rating the design rate is
required.
220 Span too low
Span is < 1 mV. Insure proper test weight or chain is
applied during span.
221 Span out of range
Span deviation > 12.5%. Consider an initial zero (P377).
Refer to
Initial Zero
on page 34.
222 Zero out of range
Zero deviation > minimum limit. Consider an initial Span
(P388). Refer to
Initial Span
on page 37.
223 Security Violation
An attempt to run command / calibration that is not
allowed under current security level.
224 Function not permitted Function not allowed under current security level.
225 BF
Flashes in the bottom right corner of display when bat-
tery charge is too low.
226
Load Cell AD’s are not func-
tioning
Consult Siemens Milltronics.
227 Err: 227 No process data available. Consult Siemens Milltronics.
228
Batch pre-act adjustment
> 10%
Pre-act adjustment is ignored. Tune process to limit batch
error.
240 Integrator not configured P002-P017 must be programmed
241 No PID mA Input
PID Process Value Source (P402) or PID Setpoint (P414)
has been programmed for a mA Input, however mA Input
Function (P255) has not been programmed properly.
242 No PID mA Output
PID System (P400) has been turned on, but mA Output
(P201) has not been programmed properly.
243 No batch setpoint relay
Batch has been set up, but no relay has been configured
for a setpoint.
PF Power Failure
Displayed at the bottom right corner of the display if
power is interrupted after the integrator has been
calibrated.