7ML19985CN01 Milltronics SF 500 – INSTRUCTION MANUAL Page 31
mmmmm
Recalibration
Calculate the span adjust value:
% span adjust =
SF 500 – material sample weight
x 100
material sample weigh
e.g. (428.5-423.0)x100
423
=1.3%
Access P019 and enter EDIT mode
Press
P019 Manual Span Adjust E
Select 1-% Change 2-Material Test 0
P598 Span Adjust Percentage V
Enter Calculated +/- error 0.00
0
kg / lb
kg / lb
1. zero calibration
start total
empty scale
4. weigh material
3. stop material feed
2. RUN mode