The following table shows the parameter of the Modbus TCP data point window:
Parameter Description
Data Type Data type supported by backend (e.g. INT).
Function
Type
Function type - depends on the type of the data (see manual of the Modbus device).
1: Read Coils,
2: Read Inputs,
3: Read Holding Registers,
4: Read Input Registers
. Currently function codes 1..4 are supported.
Slave
Number
Address/Slave number of the Modbus device.
Start
Address
Start address (offset) of the data.
Quantity Quantity of data to be read.
Configuring protocols
4.4 Overview of Modbus TCP protocol for MindConnect IoT2040
MindConnect IoT2040
System Manual 8/2023 54