UM353-1 Data Mapping
March 2003
7-5
7.2.2 Station String Data (8-bit ASCII Char - 2/Word)
Code R/W Description Range Register (MB) C/P (LIL)
STAG
R
Station Tag
12 ASCII Char
40101-40106
2/2-7
CFNR
R
Configuration File Name Reduced
8 ASCII Char
n/a
2/9-12
CFN
R
Configuration File Name
20 ASCII Char
40107-40116
7/2-7/12
SN
R
Station Serial No.
8 ASCII (0-
99999999
40117-40120
4/2-4/5
Spares 0($0000) 40121-40199
7.2.3 Station Coil Data (1-bit)
Code R/W Description Range Coil (MB) C/P (LIL)
ASE
R
1-Active Station Event
1/0
00001
3/1(0)
SEN
R/W
1-Station Event Not Ackl’d
1/0
00002
3/1(1)
FSB
R
1- Flashing Station Bargraph
1/0
00003
3/1(2)
SDV
R
1- Station Database Valid
1/0
00004
3/1(3)
CCL
R
Config Change Counter LSB (bit)
1/0
n/a
3/1(4)
CCH
R
Config Change Counter MSB (bit)
1/0
n/a
3/1(5)
SCH
R
1-Station Configuration Hold
1/0
00007
3/1(6)
SRB
R/W
1-Station Run Bit
1/0
00008
3/1(7)
OOS
R/W
1-Station Alarms Out of Service
1/0
00009
3/1(8) V2.0
(spares) 0
00010-00014
3/1(9-10)
CC1
R/W
Config Change Bit #1
1/0
n/a
3/1(11)
CC2
R/W
Config Change Bit #2
1/0
n/a
3/1(12)
CC3
R/W
Config Change Bit #3
1/0
n/a
3/1(13)
SEB
R
1-Station Error Bit
1/0
00015
3/1(14)
(spare)
0
00016
3/1(15)
spares 0($0000)
00017-00071
7.2.4 Station Status Word (SSW)
[channel 3/parameter 1]
BIT Description Value Block Read/Write Output
0 Active Station Event (ASE) 1-Active Event R
1 Station Event Not Ack’d (SEN) 1-Not Acknowledged R/W
2 Flashing Bargraph (FSB) 1-Flashing Bargraph R
3 Database Valid (SDV) 1-Valid R
4 Config Change Counter LSB 1/0 R
5 Config Change Counter MSB 1/0 R
6 Configuration Hold (SCH) 1-Hold R
7 Station Run Bit (SRB) 1-Run R
8 Stations Alarms Out of Service 1-OOS R/W
9 (not used) 0 R
10 (not used) 0 R
11 Configuration Change #1 1-Config. Changed R/W
12 Configuration Change #2 1-Config. Changed R/W
13 Configuration Change #3 1-Config. Changed R/W
14 Station Error Bit (SEB) 1-Error R