UM353-1 Data Mapping
March 2003
7-31
7.3.9 PCOM Block Status
Included in MPU Controller board firmware version 1.30 and higher.
Controller/Sequencer
Code
R/W Description Range Coil(MB) C/P (LIL)
L#INIT_OK
R/W 1-INIT_OK 1/0 09101+32(#-1) z/1(0)
L#DFAIL
R/W 1-DFAIL 1/0 09102+32(#-1) z/1(1)
L#RESET
W 1-RESET 1/0 09103+32(#-1) z/1(2)
L#START
W 1-START 1/0 09104+32(#-1) z/1(3)
L#RESTART
W 1-RESTART 1/0 09105+32(#-1) z/1(4)
L#HOLD
W 1-HOLD 1/0 09106+32(#-1) z/1(5)
L#PCOMP
W 1-PCOMP 1/0 09107+32(#-1) z/1(6)
L#ABORT
W 1-ABORT 1/0 09108+32(#-1) z/1(7)
L#READY
R 1-READY 1/0 09109+32(#-1) z/1(8)
L#RUN
R 1-RUN 1/0 09110+32(#-1) z/1(9)
L#HELD
R 1-HELD 1/0 09111+32(#-1) z/1(10)
L#DONE
R 1-DONE 1/0 09112+32(#-1) z/1(11)
L#ABORTED
R 1-ABORTED 1/0 09113+32(#-1) z/1(12)
spare
R 1/0 09114+32(#-1) z/1(13)
spare
R 1/0 09115+32(#-1) z/1(14)
spare
R 1/0 09116+32(#-1) z/1(15)
Code
R/W Description Range Coil(MB) C/P (LIL)
L#EMERG (EO)
R 1-Emerg. Override 1/0 09117+32(#-1) z+1/1(0)
L#NotAck’dEO
R/W 1-EO Not Ack’d 1/0 09118+32(#-1) z+1/1(1)
L#INTRLK (IK)
R 1-INTRLK 1/0 09119+32(#-1) z+1/1(2)
L#NotAck’d IK
R/W 1- IK Not Ack’d 1/0 09120+32(#-1) z+1/1(3)
L#FAILED (FD)
R 1-FAILED 1/0 09121+32(#-1) z+1/1(4)
L#NotAck’dFD
R/W 1- FD Not Ack’d 1/0 09122+32(#-1) z+1/1(5)
spare
R 1/0 09123+32(#-1) z+1/1(6)
spare
R 1/0 09124+32(#-1) z+1/1(7)
spare
R 1/0 09125+32(#-1) z+1/1(8)
spare
R 1/0 09126+32(#-1) z+1/1(9)
spare
R 1/0 09127+32(#-1) z+1/1(10)
spare
R 1/0 09128+32(#-1) z+1/1(11)
spare
R 1/0 09129+32(#-1) z+1/1(12)
spare
R 1/0 09130+32(#-1) z+1/1(13)
L#NotAck’dPCOM
R/W 1-PCOM Event Not Ack’d 1/0 09131+32(#-1)
z+1/1(14)
L#ACTIVEPCOM
R 1-PCOM Event is Active 1/0 09132+32(#-1) z+1/1(15)
z - LIL CHAN configured in the PCOM function block configuration.