Installation UM353-1
March 2003
8-24
8.4.13 Wiring to a Model 363 VIEWPAC Recorder
Figure 8-25 shows the wiring needed to connect a Model 363 analog input to a Moore 353 analog input. As shown,
a 1-5 Vdc transmitter input to the Moore 353 is also routed the recorder’s Analog Input 1.
5
+
_
Common Ground Bus
Earth
Ground
Analog Input,
e.g. Model 340 or
SITRANS P DSIII,
2-Wire Transmitter,
4-20 mA Output
X03109S3
18
250
1-5 Vdc
26 Vdc
H
N
External
Power
120/240 Vac
25W
47-63 Hz
Hot
Neutral
Earth Ground
Model 353A or 354/354N
Controller Terminals
G
H
N
G
A5
A6
Model 363 VIEWPAC
Recorder Terminals
Recorder
Analog Input 1,
See note 2
Recorder
Power Input
and Ground,
See note 3
Notes:
1. See UM353-1, UM354-1, or UM354N-1, Table 8.1 for AIN2, 3, and 4 terminals.
2. Recorder inputs are isolated 1-5 Vdc, Refer to UM363-1 for other Recorder analog inputs.
3. Refer to UM363-1 for power requirements and detailed wiring and grounding information.
A7
A8
+
_
Analog Input,
e.g. Model 340 or
SITRANS P DSIII,
2-Wire Transmitter,
4-20 mA Output
Power Supply
+
_
Recorder
Analog Input 2,
See note 2
AIN1
20
Station
Common
FIGURE 8-25 Moore 353 To Model 363 VIEWPAC Analog Input Wiring
8.4.14 Power Wiring
Basic connections for AC and DC power input are shown in Figure 8-26. Wiring guidelines are given in Section
8.4.2.
H
Model 353D
Rear Terminals
X03106S0
N
External
Power
120/240 Vac
25W
47-63 Hz
Hot
Neutral
Earth Ground
External
Power
24 Vdc
25W
(+)
(-)
Earth Ground
Model 353A
Rear Terminals
H
N
DC To DC
Power Supply
on
MPU Board
AC To DC
Power Supply
on
MPU Board
Controller Circuitry
Controller Circuitry
H
=Terminal on rear of case.
G
G
= Green screw at top center of rear terminal area.
G