UM353-1 Data Mapping
March 2003
7-11
7.3.4 Dynamic Loop Floating Point Data (32-bit IEEE)
Controller [ODC]
Code R/W Description Range Register (MB) C/P (LIL)
L#PF
R
Process
Real
41951+20(#-1)
n/9-10
L#SF
R/W
Setpoint
Real
41953+20(#-1)
n+1/9-10
L#VF
R/W
Valve
Real
41955+20(#-1)
n+2/9-10
L#XF
R
X Variable
Real
41957+20(#-1)
n+3/25-26
L#YF
R
Y Variable
Real
41959+20(#-1)
n+4/25-26
L#RF
R/W
Ratio
Real
41961+20(#-1)
n/23-24
L#BF
R/W
Bias
Real
41963+20(#-1)
n/25-26
L#TLF
R
Totalizer
Real
41965+20(#-1)
n+3/13-14
(spare)
($00000000)
41967+20(#-1)
(spare)
($00000000)
41969+20(#-1)
Sequencer [ODS]
Code R/W Description Range Register (MB) C/P (LIL)
L#SSNF
R/W
Sequencer Step No.*
Real
41951+20(#-1)
n/2-3
L#SAOF
R
Sequencer Analog Output
Real
41953+20(#-1)
n+1/2-3
L#SAOmF
R
Step Analog Out (most sig. word)#
Real
n/a
n+1/1
L#SAOlF
R
Step Analog Out (least sig. word)#
Real
n/a
n+2/1
L#SAEPF
R
Step Analog End Point
Real
41955+20(#-1)
n+1/4-5
L#SRTF
R/W
Step Remaining Time*
Real
41957+20(#-1)
n+3/2-3
L#SSTF
R
Sequencer Step Time
Real
41959+20(#-1)
n+3/4-5
L#SNSF
R
Sequencer Number of Steps
Real
41961+20(#-1)
n/6-7
L#SNGF
R
Sequencer Number of Groups
Real
41963+20(#-1)
n/8-9
L#SNRF
R
Sequencer Number of Recipes
Real
41965+20(#-1)
n+1/7-8
L#CRNF
Current Recipe Number @
Real
41967+20(#-1)
n+1/9-10
R/W
(spare)
0($00000000)
41969+20(#-1)
Analog Indicator [ODA] - (V2.2)
Code R/W Description Range Register (MB) C/P (LIL)
L#P1F
R
Process 1
Real
41951+20(#-1)
n/2-3
L#P2F
R
Process 2
Real
41953+20(#-1)
n+1/2-3
L#P3F
R
Process 3
Real
41955+20(#-1)
n+2/2-3
L#P4F
R
Process 4
Real
41957+20(#-1)
n+3/2-3
(spare)
0($00000000)
41959/69+20(#-1)
Discrete Indicator [ODD] & [ODP]- (V2.2)
Code
R/W Description Range Register (MB) C/P (LIL)
n/a
* A Write command will force the Step or Remaining Time to the write value.
@ The current recipe can be changed if the Sequencer is in the HOLD mode.