EasyManua.ls Logo

Siemens Moore 353 - Static Loop Integer Data

Siemens Moore 353
306 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Data Mapping UM353-1
March 2003
7-10
7.3.3 Static Loop Integer Data
Controller [ODC]
Code R/W Description Range Register (MB) C/P (LIL)
L#PGI
R/W
Proportional Gain
-9.99 to -0.01 ($1419-$17FF)
0.01 to 9.99 ($1801$1BE7)
-100.0 to -10.0 ($2418-$279C)
10.0 to 100.0 ($2864-$2BE8)
41201+30(#-1)
n/2
L#TII
R/W
Integral Time (min)
0.01 to 9.99 ($2081-$2467)
10.0 to 99.9 ($10E4-$1467)
100 to 3967 ($30E4-$3FFF)
41202+30(#-1)
n/3
L#TDI
R/W
Derivative Time (min)
0.00 to 9.99 ($2080-$2467)
10.0 to 100.0 ($10E4-$1468)
41203+30(#-1)
n/4
L#DGI
R/W
Derivative Gain
1.00 to 39.67 ($20E4--$2FFF)
41204+30(#-1)
n/5
L#MRI
R/W
Manual Reset (%)
0.0 to 100.0 ($0080-$0F80)
41205+30(#-1)
n/6
L#RHI
R
Range High
-1 to -32768 ($FFFF-$8000)
0 to 32767 ($0000-$7FFF)
41206+30(#-1)
n+3/10
L#RLI
R
Range Low
-1 to -32768 ($FFFF-$8000)
0 to 32767 ($0000-$7FFF)
41207+30(#-1)
n+3/11
L#DPPI
R
Decimal Point Position
0 to 5 ($0000-$0005)
41208+30(#-1)
n+3/12
L#PDPPI
R
Process DPP
0 to 5 ($0000-$0005)
41209+30(#-1)
n/34
L#VDPPI
R
Valve DPP
0 to 5 ($0000-$0005)
41210+30(#-1)
n+2/34
L#XDPPI
R
Variable X DPP
0 to 5 ($0000-$0005)
41211+30(#-1)
n+3/34
L#YDPPI
R
Variable Y DPP
0 to 5 ($0000-$0005)
41212+30(#-1)
n+4/34
(spare)
0 ($0000)
41213+30(#-1)
….. …..
….. ….. …..
…..
(spare)
0 ($0000)
41230+30(#-1)
Sequencer [ODS] - (MASK Configurations)
Code R/W Description Range Register (MB) C/P (LIL)
L#S006G0I
R/W
Step 6 Group 0 Input Mask
$0000-$FFFF
41201+30(#-1)
6/154
L#S006G0O
R/W
Step 6 Group 0 Output Mask
$0000-$FFFF
41202+30(#-1)
6/170
L#S006G1I
R/W
Step 6 Group 1 Input Mask
$0000-$FFFF
41203+30(#-1)
6/155
L#S006G1O
R/W
Step 6 Group 1 Output Mask
$0000-$FFFF
41204+30(#-1)
6/171
L#S006G2I
R/W
Step 6 Group 2 Input Mask
$0000-$FFFF
41205+30(#-1)
6/156
L#S006G2O
R/W
Step 6 Group 2 Output Mask
$0000-$FFFF
41206+30(#-1)
6/172
L#S007G0I
R/W
Step 7 Group 0 Input Mask
$0000-$FFFF
41207+30(#-1)
7/154
L#S007G0O
R/W
Step 7 Group 0 Output Mask
$0000-$FFFF
41208+30(#-1)
7/170
….. ….. ….. ….. ….. …..
L#S009G2I
R/W
Step 9 Group 2 Input Mask
$0000-$FFFF
41223+30(#-1)
9/156
L#S009G2O
R/W
Step 9 Group 2 Output Mask
$0000-$FFFF
41224+30(#-1)
9/172
L#S010G0I
R/W
Step 10 Group 0 Input Mask
$0000-$FFFF
41225+30(#-1)
10/154
L#S010G0O
R/W
Step 10 Group 0 Output Mask
$0000-$FFFF
41226+30(#-1)
10/170
L#S010G1I
R/W
Step 10 Group 1 Input Mask
$0000-$FFFF
41227+30(#-1)
10/155
L#S010G1O
R/W
Step 10 Group 1 Output Mask
$0000-$FFFF
41228+30(#-1)
10/171
L#S010G2I
R/W
Step 10 Group 2 Input Mask
$0000-$FFFF
41229+30(#-1)
10/156
L#S010G2O
R/W
Step 10 Group 2 Output Mask
$0000-$FFFF
41230+30(#-1)
10/172
Analog, Discrete, & Pushbutton Indicators [ODA] ODD] [ODP]- (V2.1)
Code R/W Description Range Register (MB) C/P (LIL)
n/a ****
**** NOTE: Registers (40451-40480) are reserved for ASCII Tags when the ODP display has been selected in
configuration
StockCheck.com

Table of Contents

Related product manuals