UM353-1 Data Mapping
March 2003
7-9
Analog Indicator [ODA] - (V2.2)
Code R/W Description Range Register (MB) C/P (LIL)
L#P1ALI
R/W
Process 1 Alarm A Limit (%)
-3.3 to 103.3 ($0-$0FFF)
40451+30(#-1)
n+1/13
L#P1BLI
R/W
Process 1 Alarm B Limit (%)
-3.3 to 103.3 ($0-$0FFF)
40452+30(#-1)
n+1/14
L#P2ALI
R/W
Process 2 Alarm A Limit (%)
-3.3 to 103.3 ($0-$0FFF)
40453+30(#-1)
n+1/15
L#P2BLI
R/W
Process 2 Alarm B Limit (%)
-3.3 to 103.3 ($0-$0FFF)
40454+30(#-1)
n+1/16
L#P3ALI
R/W
Process 3 Alarm A Limit (%)
-3.3 to 103.3 ($0-$0FFF)
40455+30(#-1)
n+1/17
L#P3BLI
R/W
Process 3 Alarm B Limit (%)
-3.3 to 103.3 ($0-$0FFF)
40456+30(#-1)
n+1/18
L#P4ALI
R/W
Process 4 Alarm A Limit (%)
-3.3 to 103.3 ($0-$0FFF)
40457+30(#-1)
n+1/19
L#P4BLI
R/W
Process 4 Alarm B Limit (%)
-3.3 to 103.3 ($0-$0FFF)
40458+30(#-1)
n+1/20
L#P1ATI R/W Process 1 Alarm A Type
0-3 ($0000-$0003)
40459+30(#-1)
n+2/13
L#P1BTI R/W Process 1 Alarm B Type
0-3 ($0000-$0003)
40460+30(#-1)
n+2/14
L#P2ATI R/W Process 2 Alarm A Type
0-3 ($0000-$0003)
40461+30(#-1)
n+2/15
L#P2BTI R/W Process 2 Alarm B Type
0-3 ($0000-$0003)
40462+30(#-1)
n+2/16
L#P3ATI R/W Process 3 Alarm A Type
0-3 ($0000-$0003)
40463+30(#-1)
n+2/17
L#P3BTI R/W Process 3 Alarm B Type
0-3 ($0000-$0003)
40464+30(#-1)
n+2/18
L#P4ATI R/W Process 4 Alarm A Type
0-3 ($0000-$0003)
40465+30(#-1)
n+2/19
L#P4BTI R/W Process 4 Alarm B Type
0-3 ($0000-$0003)
40466+30(#-1)
n+2/20
L#P1API R/W Process 1 Alarm A Priority
1-5 ($0001-$0005)
40467+30(#-1)
n+3/13
L#P1BPI R/W Process 1 Alarm B Priority
1-5 ($0001-$0005)
40468+30(#-1)
n+3/14
L#P2API
R/W
Process 2 Alarm A Priority
1-5 ($0001-$0005) 40469+30(#-1) n+3/15
L#P2BPI
R/W
Process 2 Alarm B Priority
1-5 ($0001-$0005) 40470+30(#-1) n+3/16
L#P3API
R/W
Process 3 Alarm A Priority
1-5 ($0001-$0005) 40471+30(#-1) n+3/17
L#P3BPI
R/W
Process 3 Alarm B Priority
1-5 ($0001-$0005) 40472+30(#-1) n+3/18
L#P4API
R/W
Process 4 Alarm A Priority
1-5 ($0001-$0005) 40473+30(#-1) n+3/19
L#P4BPI
R/W
Process 4 Alarm B Priority
1-5 ($0001-$0005) 40474+30(#-1) n+3/20
….. ….. ….. ….. ….. …..
(spare) 0 ($0000) 40480+30(#-1)
Discrete Indicator [ODD] - (V2.2)
Code R/W Description Range Register (MB) C/P (LIL)
n/a
Discrete Indicator [ODP] - (V2.2)
Code R/W Description Range Register (MB) C/P (LIL)
n/a ****
**** NOTE: Registers (40451-40480) are reserved for ASCII Tags when the ODP display has been selected in
configuration.