UM353-1 Function Blocks
March 2003
3-41
3.2.33 DIL_ - Discrete Input _ LIL
DIL_ function blocks are available when the optional LIL
communication board is installed. DIL block numbers are
assigned in sequence with each use, station wide. The block
allows the station to obtain a global word (GW) from another
station on the LIL.
The function block has 16 outputs, D0 through DF, which
represent the values of bits 0-F in the global word. Output QS
indicates the quality of the received data and will go high (1)
when the data is bad. This is normally associated with failure to
receive global data due to a LIL failure or a misconfiguration of
the source.
The received global word will also be re-transmitted by this station as a parameter 1 value in the configured channel
n.
1 2 3 4 5 6 7 8 9 10` 11 12
n GW SA/SC
DISCRETE (WORD) INPUT - LIL
DISCRETE (WORD)
DIL_
LIL
CHAN
nel
(H)
..........
008 to 255
(null)
INPUT - LIL
D0
Output
D0
DF
Output
DF
N
H
C
A
L
I
L
SRCE ADD
SRCE CHN
S
ou
RCE
ADD
ress
(H)
......
00 to 64
(null)
S
ou
RCE
CH
a
N
nel
(H)
.. 000 to 255
(null)
QS
Output
QS
LIL
GLOBAL
DATA
StockCheck.com