EasyManua.ls Logo

Siemens Moore 353 - Dynamic Loop Integer Data

Siemens Moore 353
306 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
UM353-1 Data Mapping
March 2003
7-7
7.3.1 Dynamic Loop Integer Data
Controller [ODC]
Code R/W Description Range Register (MB) C/P (LIL)
L#PI
R
Process (%)
-3.3 to 103.3 ($0-$0FFF)
40201+10(#-1)
n/1
L#SI
R/W
Setpoint (%)
-3.3 to 103.3 ($0-$0FFF)
40202+10(#-1)
n+1/1
L#VI
R/W
Valve (%)
-3.3 to 103.3 ($0-$0FFF)
40203+10(#-1)
n+2/1
L#XI
R
X Variable (%)
-3.3 to 103.3 ($0-$0FFF)
40204+10(#-1)
n+3/24
L#YI
R
Y Variable (%)
-3.3 to 103.3 ($0-$0FFF)
40205+10(#-1)
n+4/24
L#RI
R/W
Ratio
0.00 to 38.40($80-$0F80)
40206+10(#-1)
n/7
L#BI
R/W
Bias
100-0-100 ($80-$0F80)
40207+10(#-1)
n/8
L#TlmI
R
Totalizer - 3 ms (whole) digits
0-999 ($0000-$03E7)
40208+10(#-1)
n+2/2
L#TllI
R
Totalizer - 3 ls (whole) digits
0-999 ($0000-$03E7)
40209+10(#-1)
n+2/3
CLS
R/W
Control Loop Status
(see CLS)
(see coils)
n+3/1
ASW
R/W
Alarm Status Word
(see ASW)
(see coils)
n+4/1
L#PCSW
R
PCOM Block Status Word (V1.3)
1-7 ($0001-$0007)
40210+10(#-1)
z+2/1
Sequencer [ODS]
Code R/W Description Range Register (MB) C/P (LIL)
L#SSNI
R
Sequencer Step No.
0-250 ($0000-$00FA)
40201+10(#-1)
n/1
L#SNSI
R
Sequencer Number of Steps
0-250 ($0000-$00FA)
40202+10(#-1)
n/4
L#SNGI
R
Sequencer Number of Groups
0-16 ($0000-$0010)
40203+10(#-1)
n/5
L#SLS
R/W
Sequencer Loop Status
(see SLS)
(see coils)
n+5/1
L#SNRI
R
Sequencer Number of Recipes
0-9 ($0000-$0009)
40204+10(#-1)
n/11
L#CRNI
R/W
Current Recipe Number
0-9 ($0000-$0009)
40205+10(#-1)
n+3/1
L#PCSW
R
PCOM Block Status Word (V1.3)
1-7 ($0001-$0007)
40206+10(#-1)
z+2/1
L#TACM
R
Total Active Conditional Msgs
(V1.3)
0-64 $0000-$0040)
40207+10(#-1)
n/43
(spare)
0 ($0000)
40208+10(#-1)
….. ….. ….. ….. ….. …..
(spare)
0 ($0000)
40210+10(#-1)
Analog Indicator [ODA] - (V2.2)
Code R/W Description Range Register (MB) C/P (LIL)
L#P1I
R
Process 1 (%)
-3.3 to 103.3 ($0-$0FFF)
40201+10(#-1)
n/1
L#P2I
R
Process 2 (%)
-3.3 to 103.3 ($0-$0FFF)
40202+10(#-1)
n+1/1
L#P3I
R
Process 3 (%)
-3.3 to 103.3 ($0-$0FFF)
40203+10(#-1)
n+2/1
L#P4I
R
Process 4 (%)
-3.3 to 103.3 ($0-$0FFF)
40204+10(#-1)
n+3/1
L#SW1 R/W Status Word 1 (see SW1) (see coils) n+4/1
L#SW2 R/W Status Word 2 (see SW1) (see coils) n+5/1
Discrete Indicator [ODD] - (V2.2)
Code R/W Description Range Register (MB) C/P (LIL)
L#DISW
R/W Discrete Input Status Word (see L#DISW) (see coils) n/1
L#DSSW
R/W Discrete State Status Word (see L#DSSW) (see coils) n+1/1
L#DOSW
R/W Discrete Output Status Word (see L#DOSW) (see coils) n+2/1
L#SW
R/W Status Word (see L#SW) (see coils) n+3/1
Discrete Indicator [ODP] - (V2.2)
Code
R/W Description Range Register (MB) C/P (LIL)
L#SW1
R/W Status Word 1 (see L#SW1) (see coils) n/1
L#SW2
R/W Status Word 2 (see L#SW2) (see coils) n+1/1
StockCheck.com