7.3.12 Trend Data (Loop Defined by MLTP)
Included in MPU Controller board firmware version 1.30 and higher.
Code
R/W Description Range Register (MB) C/P (LIL)
A1RMN R ATD01 MIN SCALE Real 48001 n/a
A1RMX R ATD01 MAX SCALE Real 48003 n/a
A1DPP R ATD01 Decimal Point Position 0-5 48005 n/a
A1EU R ATD01 Engineering Units 6 ASCII Char 48006 n/a
A1YR R ATD01 Year V2.0 (5) 1997- 48009 n/a
A1MT R ATD01 Month V2.0 (5) 1-12 48010 n/a
A1DY R ATD01 Day V2.0 (5) 1-31 48011 n/a
A1HR R ATD01 Hour V2.0 (5) 0-23 48012 n/a
A1MN R ATD01 Minute V2.0 (5) 0-59 48013 n/a
A1SC R ATD01 Second V2.0 (5) 0-59 48014 n/a
A1ST R/W* ATD01 Sample Time x0.01=min 1-48000 48015 n/a
A1STC R ATD01 % Sample Time Complete 0-1000 (x.1=%) 48016 n/a
A1D1 R ATD01 Data 1 (latest) 0-100% 128-3968 48017 n/a
A1D2 R ATD01 Data 2 0-100% 128-3968 48018 n/a
A1D3 R ATD01 Data 3 0-100% 128-3968 48019 n/a
....................................................................................................................................................................
A1D168 R ATD01 Data 168 0-100% 128-3968 48184 n/a
A1D169 R ATD01 Data 169 0-100% 128-3968 48185 n/a
A1D170 R ATD01 Data 170 0-100% 128-3968 48186 n/a
* Writing to the sample time will reset all data points A1D1 through A1D170 to $0.
A2RMN R ATD02 MIN SCALE Real 48201 n/a
A2RMX R ATD02 MAX SCALE Real 48203 n/a
A2DPP R ATD02 Decimal Point Position 0-5 48205 n/a
A2EU R ATD02 Engineering Units 6 ASCII Char 48206 n/a
A2YR R ATD02 Year V2.0 (5) 1997 48209 n/a
A2MT R ATD02 Month V2.0 (5) 1-12 48210 n/a
A2DY R ATD02 Day V2.0 (5) 1-31 48211 n/a
A2HR R ATD02 Hour V2.0 (5) 0-23 48212 n/a
A2MN R ATD02 Minute V2.0 (5) 0-59 48213 n/a
A2SC R ATD02 Second V2.0 (5) 0-59 48214 n/a
A2ST R/W* ATD02 Sample Time x0.01=min 1-48000 48215 n/a
A2STC R ATD02 % Sample Time Complete 0-1000 (x.1=%) 48216 n/a
A2D1 R ATD02 Data 1 (latest) 0-100% 128-3968 48217 n/a
A2D2 R ATD02 Data 2 0-100% 128-3968 48218 n/a
A2D3 R ATD02 Data 3 0-100% 128-3968 48219 n/a
....................................................................................................................................................................
A2D168 R ATD02 Data 168 0-100% 128-3968 48384 n/a
A2D169 R ATD02 Data 169 0-100% 128-3968 48385 n/a
A2D170 R ATD02 Data 170 0-100% 128-3968 48386 n/a
* Writing to the sample time will reset all data points A2D1 through A2D170 to $0.