Data Mapping UM353-1
March 2003
7-18
L#G3Tag R Group 3 Tag 6 ASCII Char 45499+100(#-1) n/37-39
L#G3P1T R Group 3 PB1 Tag 6 ASCII Char 45502+100(#-1) n/40-42
L#G3P2T R Group 3 PB2 Tag 6 ASCII Char 45505+100(#-1) n/43-45
L#G3SAT R Group 3 Switch Position A Tag 6 ASCII Char 45508+100(#-1) n/46-48
L#G3SMT R Group 3 Switch Position M Tag 6 ASCII Char 45511+100(#-1) n+1/46-48
L#G3F1T R Group 3 Feedback 1 Tag 6 ASCII Char 45514+100(#-1) n+1/37-39
L#G3F0T R Group 3 Feedback 0 Tag 6 ASCII Char 45517+100(#-1) n+1/40-42
L#G4Tag R Group 4 Tag 6 ASCII Char 45520+100(#-1) n/49-51
L#G4P1T R Group 4 PB1 Tag 6 ASCII Char 45523+100(#-1) n/52-54
L#G4P2T R Group 4 PB2 Tag 6 ASCII Char 45526+100(#-1) n/55-57
L#G4SAT R Group 4 Switch Position A Tag 6 ASCII Char 45529+100(#-1) n/58-60
L#G4SMT R Group 4 Switch Position M Tag 6 ASCII Char 45532+100(#-1) n+1/58-60
L#G4F1T R Group 4 Feedback 1 Tag 6 ASCII Char 45535+100(#-1) n+1/49-51
L#G4F0T R Group 4 Feedback 0 Tag 6 ASCII Char 45538+100(#-1) n+1/52-54
L#G5Tag R Group 5 Tag 6 ASCII Char 40451+30(#-1) n/61-63
L#G5P1T R Group 5 PB1 Tag 6 ASCII Char 40454+30(#-1) n/64-66
L#G5P2T R Group 5 PB2 Tag 6 ASCII Char 40457+30(#-1) n/67-69
L#G5SAT R Group 5 Switch Position A Tag 6 ASCII Char 40460+30(#-1) n/70-72
L#G5SMT R Group 5 Switch Position M Tag 6 ASCII Char 40463+30(#-1) n+1/70-72
L#G5F1T R Group 5 Feedback 1 Tag 6 ASCII Char 40466+30(#-1) n+1/61-63
L#G5F0T R Group 5 Feedback 0 Tag 6 ASCII Char 40469+30(#-1) n+1/64-66
Spares 40472-40480
Note: These Modbus groupings normally used for Variable Loop Integer Data with displays other than ODP
L#G6Tag R Group 6 Tag 6 ASCII Char 41201+30(#-1) n/73-75
L#G6P1T R Group 6 PB1 Tag 6 ASCII Char 41204+30(#-1) n/76-78
L#G6P2T R Group 6 PB2 Tag 6 ASCII Char 41207+30(#-1) n/79-81
L#G6SAT R Group 6 Switch Position A Tag 6 ASCII Char 41210+30(#-1) n/82-84
L#G6SMT R Group 6 Switch Position M Tag 6 ASCII Char 41213+30(#-1) n+1/82-84
L#G6F1T R Group 6 Feedback 1 Tag 6 ASCII Char 41216+30(#-1) n+1/73-75
L#G6F0T R Group 6 Feedback 0 Tag 6 ASCII Char 41219+30(#-1) n+1/76-78
spares 41222-41230
Note: These Modbus groupings normally used for Static Loop Integer Data with displays other than ODP
L#G7Tag R Group 7 Tag 6 ASCII Char 42451+60(#-1) n/85-87
L#G7P1T R Group 7 PB1 Tag 6 ASCII Char 42454+60(#-1) n/88-90
L#G7P2T R Group 7 PB2 Tag 6 ASCII Char 42457+60(#-1) n/91-93
L#G7SAT R Group 7 Switch Position A Tag 6 ASCII Char 42460+60(#-1) n/94-96
L#G7SMT R Group 7 Switch Position M Tag 6 ASCII Char 42463+60(#-1) n+1/94-96
L#G7F1T R Group 7 Feedback 1 Tag 6 ASCII Char 42466+60(#-1) n+1/85-87
L#G7F0T R Group 7 Feedback 0 Tag 6 ASCII Char 42469+60(#-1) n+1/88-90
L#G8Tag R Group 8 Tag 6 ASCII Char 42472+60(#-1) n/97-99
L#G8P1T R Group 8 PB1 Tag 6 ASCII Char 42475+60(#-1) n/100-102
L#G8P2T R Group 8 PB2 Tag 6 ASCII Char 42478+60(#-1) n/103-105
L#G8SAT R Group 8 Switch Position A Tag 6 ASCII Char 42481+60(#-1) n/106-108
L#G8SMT R Group 8 Switch Position M Tag 6 ASCII Char 42484+60(#-1) n+1/106-108
L#G8F1T R Group 8 Feedback 1 Tag 6 ASCII Char 42487+60(#-1) n+1/97-99
L#G8F0T R Group 8 Feedback 0 Tag 6 ASCII Char 42490+60(#-1) n+1/100-102
spares 42493-42509
Note: These Modbus groupings normally used for Variable Loop Floating Point Data with displays other than ODP