Installation UM353-1
March 2003
8-12
TABLE 8.1 Rear Terminal Assignments
CONTROLLER BOARD
I/O EXPANDER BOARD
Description
ID
#
# ID Description
Power - AC Hot/ DC +
ACH/DC+ H 27 ROUT1nc
Relay Output 1 Normally Closed
Power - AC Neutral/DC -
ACN/DC- N 28 ROUT1c
Relay Output 1 Common
Network Communication A
NCA 3 29 ROUT1no
Relay Output 1 Normally Open
Network Communication B
NCB 4 30 ROUT2nc
Relay Output 2 Normally Closed
Transmitter Power 26Vdc +
XMTR+ 5 31 ROUT2c
Relay Output 2 Common
Transmitter/Station Common
COM 6 32 ROUT2no
Relay Output 2 Normally Open
Transmitter Power 26Vdc +
XMTR+ 7 33 AOUT3+
Analog Output 3 +
Digital Output 1 +
DOUT1+ 8 34 AOUTC
Analog Output 3 Common
Digital Outputs 1/2 Common
DOUTC 9 35 DINU1+
Digital Input Universal 1 +
Digital Output 2 +
DOUT2+ 10 36 DINU1-
Digital Input Universal 1 -
Digital Input 1 +
DIN1+ 11 37 DINU2+
Digital Input Universal 2 +
Digital Input 1 -
DIN1- 12 38 DINU2-
Digital Input Universal 2 -
Digital Input 2 +
DIN2+ 13 39 XMTR+
Transmitter Power 26Vdc +
Digital Input 2 -
DIN2- 14 40 COM
Transmitter/Station Common
Digital Input 3 +
DIN3+ 15 41 AIN4+
Analog Input 4 +
Digital Input 3 -
DIN3- 16 42 AINC
Analog Input Common
Analog Output 1 +
AOUT1+ 17 43 DIN4+
Digital Input 4 +
Analog Output 1/2 Common
AOUTC 18 44 DIN4-
Digital Input 4 -
Analog Output 2 +
AOUT2+ 19 45 AINU1a
Analog Input Universal 1 a
Analog Input 1 +
AIN1+ 20 46 AINU1b
Analog Input Universal 1 b
Analog Input 1/2 Common
AINC 21 47 AINU1c
Analog Input Universal 1 c
Analog Input 2 +
AIN2+ 22 48 AINU1d
Analog Input Universal 1 d
Analog Input 3 +
AIN3+ 23 49 AINU2a
Analog Input Universal 2 a
Analog Input 3 Common
AINC 24 50 AINU2b
Analog Input Universal 2 b
I/O Bus A
IOA 25 51 AINU2c
Analog Input Universal 2 c
I/O Bus B
IOB 26 52 AINU2d
Analog Input Universal 2 d
Notes:
1. Use this table for both direct entry (green or gray connectors) and side entry (black connectors) terminal styles.
2. # - Terminal letters and numbers are printed on individual connectors. Model 353_1_N… has 2 connectors;
Model 353_2_1… has 4 connectors and an I/O Expander board. (Underscore is a placeholder/wildcard; ellipsis
indicates that subsequent characters do not affect selection.)
3. Safety/Case Ground - Wire to green screw at top center of rear terminal area.
4. NCA and NCB - Connect LIL Twinaxial Cable or twisted pair wiring. Refer to Section 8.5 for additional
information.
5. IOA and IOB - LonWorks bus connections. Twisted pair wiring is typical.
6. Ground Bus - An external, user-supplied ground bus can ease connection of multiple grounds, particularly
when twinaxial cable shields are to be grounded.