EasyManua.ls Logo

Siemens Moore 353 - Page 229

Siemens Moore 353
306 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
UM353-1 Installation
March 2003
8-17
+
_
5
8
(+)
(-)
Common Ground Bus
26 Vdc
Earth
Ground
Controller Terminals
Common
9
Controller Circuitry
_
Digital Output
5
8
(+)
(-)
Common Ground Bus
26 Vdc
Earth
Ground
Controller Terminals
Common
9
Controller Circuitry
_
Digital Output
X03112S3
B. Voltage Output, Non-Isolated
A. Current Output, Isolated
5
8
Inductive Load with
Suppression Diode,
See Note
Common Ground Bus
26 Vdc
Earth
Ground
Controller Terminals
Common
9
Controller Circuitry
_
Digital Output
24 Vdc
Resistive Load
Resistive Load
C. Current Output, Isolated
Notes:
1. Inductive load must be shunted with a transient
suppression diode (1N4005 or equiv.) to prevent
damage to station output circuit.
2. See Table 8.1 for DOUT2 terminal numbers.
10K Typical
Figure 8-15 Digital Output DOUT1, Resistive and Inductive Loads
StockCheck.com

Table of Contents

Related product manuals