Calibration UM353-1
March 2003
12-4
17. If all points have been calibrated and verified, press EXIT button to leave calibration mode and enter operation
mode. If additional function blocks are to be calibrated and verified, press STEP UP button to enter
FUNCTION BLOCK level. Perform steps 2-19 for each function block.
If security is enabled, the exiting the configuration mode will lock out the calibration mode until the security
combination is re-entered.