Model Designation and Specifications UM353-1
March 2003
14-2
TABLE 14.1 Moore 353 Model Designation*
353 PROCESS AUTOMATION CONTROLLER
MPU Controller Board
A
120/240 Vac (85-264 Vac), 47-63 Hz.
D 24 Vdc, +20%, -15%
Mounting Case
1 Case with 26 Terminals; not expandable to 52 terminals - Discontinued
2 Case with 52 Terminals (Black Side Entry Connectors) - Discontinued
4 Case with 52 Terminals (Gray or Green Direct Entry Connectors) and Ethernet Connector
5 High Shock and Vibration Case with Ethernet Connector (requires Electrical Approval “N Not Required”)
Operator’s Display Panel (Display Assembly)
F Fixed Analog & Digital Displays
I/O Expansion
N Not Required
1 Local I/O Expander (e.g., T/C, RTD, Frequency, Relay)
Option Board A-1, Remote I/O Communications
N Not Required
L
LonWorks Protocol
Option Board A-2
N Not Required
Option Board B-1, Network Communications
N Not Required
E Ethernet
L Local Instrument Link (LIL)
Option Board B-2, Real Time Clock/Configuration Backup
N Not Required
R Removable Configuration Board (RCB) - Discontinued
T Real Time Clock/Configuration Backup Board (RTC/CB)
Modification Options
N
Not Required
X Controller Modified as detailed in order bill of material
Reserved for Future Use
N Reserved for Future Use
Design Level
A Design Level A
Electrical Approval
N
Not Required
4 FM/CSA Division 2 Class 1 Groups A, B, C & D suitable for
non-incendive (CE compliant)
W FM/CSA Division 2 Class 1 Groups A, B, C & D suitable for
non-incendive (CE compliant and ABS approved)
X
FM/CSA Division 2 Class 1 Groups A, B, C & D suitable for
non-incendive
353A 4 F N N N N N N N A N Sample Model No.
Contact Siemens Energy & Automation, Process Instrumentation for the latest model designation information, availability of
some options, and current electrical approvals. Always refer to the labels on the controller case for approvals and
certifications.