Parameter Value range Default Parameter reas‐
signment in
RUN
Eciency range
Measurement type
(Page 25)
• Disabled
• Current (2-wire transducer)
• Current (4‑wire transducer)
Current (2-wire
transducer)
Yes Channel
Measuring range (Page 25)
• 0 to 20 mA
• 4 to 20 mA
• 4 to 20 mA HART
There is no underrange in the meas‐
uring range 0 to 20 mA. That is, the
smallest analog value is zero.
4 to 20 mA HART Yes Channel
Interference frequency sup‐
pression (Page 26)
• 60 Hz
(integration time 16.6 ms)
• 50 Hz
(integration time 20 ms)
• 10 Hz
(integration time 100 ms)
When 50 Hz is set, the interference
signals of 400 Hz are ltered auto‐
matically.
10 Hz Yes Channel
Smoothing (Page 26)
• None
• Weak
• Medium
• Strong
None Yes Channel
Number of HART repetitions
(Page 27)
0 to 10 5 Yes Channel
Failure monitoring accord‐
ing to NE43 (Page 27)
• Enabled
• Disabled
Disabled Yes Channel
Diagnostics HART (Page 28)
• Enabled
• Disabled
Enabled Yes Channel
Diagnostics overow
(Page 28)
• Enabled
• Disabled
Enabled Yes Channel
Diagnostics underow
(Page 28)
• Enabled
• Disabled
Enabled Yes Channel
Diagnostics, Wire break
(Page 29)
• Enabled
• Disabled
Enabled Yes Channel
Diagnostics encoder supply
(Page 29)
• Enabled
• Disabled
Enabled Yes Channel
Hardware interrupt high lim‐
it 1/2 (Page 29)
• Enabled
• Disabled
Disabled Yes Channel
Hardware interrupt low limit
1/2 (Page 29)
• Enabled
• Disabled
Disabled Yes Channel
Parameters
5.3 Module/channel parameters
AI 4xI 2-/4-wire HART ISOL HA
Equipment Manual, 07/2022, A5E50101523-AB 23