Parameter Value range Default Parameter reas‐
signment in
RUN
E󹪟ciency range
Measurement type
(Page 25)
Disabled
Current (2-wire transducer)
Current (4‑wire transducer)
Current (2-wire
transducer)
Yes Channel
Measuring range (Page 25)
0 to 20 mA
4 to 20 mA
4 to 20 mA HART
There is no underrange in the meas‐
uring range 0 to 20 mA. That is, the
smallest analog value is zero.
4 to 20 mA HART Yes Channel
Interference frequency sup‐
pression (Page 26)
60 Hz
(integration time 16.6 ms)
50 Hz
(integration time 20 ms)
10 Hz
(integration time 100 ms)
When 50 Hz is set, the interference
signals of 400 Hz are 󹪝ltered auto‐
matically.
10 Hz Yes Channel
Smoothing (Page 26)
None
Weak
Medium
Strong
None Yes Channel
Number of HART repetitions
(Page 27)
0 to 10 5 Yes Channel
Failure monitoring accord‐
ing to NE43 (Page 27)
Enabled
Disabled
Disabled Yes Channel
Diagnostics HART (Page 28)
Enabled
Disabled
Enabled Yes Channel
Diagnostics over󹪞ow
(Page 28)
Enabled
Disabled
Enabled Yes Channel
Diagnostics under󹪞ow
(Page 28)
Enabled
Disabled
Enabled Yes Channel
Diagnostics, Wire break
(Page 29)
Enabled
Disabled
Enabled Yes Channel
Diagnostics encoder supply
(Page 29)
Enabled
Disabled
Enabled Yes Channel
Hardware interrupt high lim‐
it 1/2 (Page 29)
Enabled
Disabled
Disabled Yes Channel
Hardware interrupt low limit
1/2 (Page 29)
Enabled
Disabled
Disabled Yes Channel
Parameters
5.3 Module/channel parameters
AI 4xI 2-/4-wire HART ISOL HA
Equipment Manual, 07/2022, A5E50101523-AB 23