Maintenance
message
Error
code
Assignment Meaning / Cause Remedy
Retentive memo‐
ry in carrier mod‐
ule defective
154
H
Module Fault detected in the data block on the carrier
module during operation
Replace carrier module
Retentive memo‐
ry in the terminal
block defective
155
H
Module A memory block error was detected on the
terminal block during operation
Replace terminal block
1
Response of the HART con󹪝guration changed maintenance message
If the HART 󹪝eld device signals "parameter reassignment" (con󹪝guration changed) in the 2nd
status byte, the module generates the maintenance message "HART con󹪝guration changed". If
the 󹪝eld device withdraws the message in the 2nd status byte within a minute, the maintenance
message is also deleted again by the module. If the message in the 2nd status byte is still set after
a minute, the module then independently sends HART command 38 for resetting the message
in the 󹪝eld device.
A.6 Hardware interrupts
Hardware interrupts
The I/O module can initiate hardware interrupts when limit violations of analog input signals
occur.
Interrupt OBs are called automatically if an interrupt occurs.
You can 󹪝nd detailed information on the event in the hardware interrupt organization block with
the "RALRM" instruction (read additional interrupt information).
The module generates a hardware interrupt at the following events:
Violation of the low limit 1
Violation of the high limit 1
Violation of the low limit 2
Violation of the high limit 2
The module analog input (channel) that has triggered the hardware interrupt is entered in
variable OB40_POINT_ADDR in the start information of OB40. The 󹪝gure below shows the
assignment to the bits of local data double word 8.
Parameters, diagnostics messages and address space
A.6 Hardware interrupts
AI 4xI 2-/4-wire HART ISOL HA
Equipment Manual, 07/2022, A5E50101523-AB 67