Maintenance
message
Error
code
Assignment Meaning / Cause Remedy
HART primary var‐
iable outside of
limits
142
H
Analog input
Incorrect parameters in the HART 󹪝eld
device
HART 󹪝eld device is set to "Primary varia‐
ble outside of limits" in simulation mode
Incorrect measuring point
Parameter assignment of primary varia‐
ble outside of limits
Check the parameter as‐
signment of the HART de‐
vice
Correct the simulation
Check whether the correct
measuring transducer is
connected
HART analog out‐
put current of the
󹪝eld device is satu‐
rated
143
H
Analog input
The output current of the HART 󹪝eld de‐
vice is saturated:
Incorrect parameters in the HART 󹪝eld
device
HART 󹪝eld device is set to a measured
value that is too high in simulation mode
Incorrect measuring point
HART output cur‐
rent of the 󹪝eld de‐
vice speci󹪝ed
144
H
Analog input
The output current of the HART 󹪝eld de‐
vice is 󹪝xed:
Incorrect parameters in the HART 󹪝eld
device
HART 󹪝eld device is set to a measured
value that is too high in simulation mode
Incorrect measuring point
HART additional
status informa‐
tion available
145
H
Analog input In the HART device status (in the 2nd status
byte), the HART 󹪝eld device identi󹪝er for "fur‐
ther status information available" has been
set
Read out status with HART com‐
mand 48 and clear error/cause
if necessary
HART con󹪝gura‐
tion changed
1
146
H
Analog input In the HART device status (in the 2nd status
byte), the identi󹪝er for "parameter reassign‐
ment" of the HART 󹪝eld device has been set
If no diagnostics interrupt is to
be triggered by recon󹪝gura‐
tion, the HART diagnostics
must be disabled.
HART malfunction
in the 󹪝eld device
147
H
Analog input In the HART device status (in the 2nd status
byte) the 󹪝eld device reports a malfunction
Read out status with HART
command 48 and clear er‐
ror/cause if necessary
Replace the 󹪝eld device
HART secondary
variable outside
the limits
149
H
Analog input
Incorrect parameters in the HART 󹪝eld
device
HART 󹪝eld device is set to "Non-primary
variable outside limits" in simulation
mode
Incorrect measuring point
Parameter assignment of non-primary
variable is outside the limits
Check the parameter as‐
signment of the HART de‐
vice
Correct the simulation
Check whether the correct
measuring transducer is
connected
Parameters, diagnostics messages and address space
A.5 Maintenance events
AI 4xI 2-/4-wire HART ISOL HA
66 Equipment Manual, 07/2022, A5E50101523-AB