Description
The parameters are divided into three types:
Module/channel parameters (data record 128)
Parameters which determine the display of HART variables in the address space of the
module; HART mapping parameters (data record 130)
System parameters (potential group, IO redundancy)
Note
With the exception of parameter assignment of the potential group, all parameters can be
changed when the CPU is in RUN.
5.3 Module/channel parameters
De󹪝nition
Module/channel parameters are speci󹪝c parameters whose con󹪝guration can a󹪜ect the entire
module or channels.
Description
The following module/channel parameters are available:
Note
Unused channels
"Disable" unused channels in the parameter assignment to improve the cycle time of the module.
A disabled channel always supplies the analog value 7FFF
H
.
Parameter Value range Default Parameter reas‐
signment in
RUN
E󹪟ciency range
Diagnostics, Missing supply
voltage L+ (Page 24)
Enabled
Disabled
Enabled Yes Module
IO redundancy (Page 24)
None
2 modules
None Yes Module
Potential group (Page 25)
Use potential group of the left
module (dark gray TB)
Form a new potential group
(light gray TB)
No potential group (black TB)
Use potential
group of the left
module
No Module
Parameters
5.3 Module/channel parameters
AI 4xI 2-/4-wire HART ISOL HA
22 Equipment Manual, 07/2022, A5E50101523-AB