Description
The parameters are divided into three types:
• Module/channel parameters (data record 128)
• Parameters which determine the display of HART variables in the address space of the
module; HART mapping parameters (data record 130)
• System parameters (potential group, IO redundancy)
Note
With the exception of parameter assignment of the potential group, all parameters can be
changed when the CPU is in RUN.
5.3 Module/channel parameters
Denition
Module/channel parameters are specic parameters whose conguration can aect the entire
module or channels.
Description
The following module/channel parameters are available:
Note
Unused channels
"Disable" unused channels in the parameter assignment to improve the cycle time of the module.
A disabled channel always supplies the analog value 7FFF
H
.
Parameter Value range Default Parameter reas‐
signment in
RUN
Eciency range
Diagnostics, Missing supply
voltage L+ (Page 24)
• Enabled
• Disabled
Enabled Yes Module
IO redundancy (Page 24)
• None
• 2 modules
None Yes Module
Potential group (Page 25)
• Use potential group of the left
module (dark gray TB)
• Form a new potential group
(light gray TB)
• No potential group (black TB)
Use potential
group of the left
module
No Module
Parameters
5.3 Module/channel parameters
AI 4xI 2-/4-wire HART ISOL HA
22 Equipment Manual, 07/2022, A5E50101523-AB