Analog value display
C
C.1 Analog value display in the current measurement range 0 to 20 mA
Table C-1 Representation / current measuring ranges 0 to 20 mA
Values Current measuring range Range
Dec. Hex. 0 to 20 mA
32767 7FFF >23.52 mA Overow
32511 7EFF 23.52 mA Overrange
27649 6C01
27648 6C00 20 mA Nominal range
20736 5100 15 mA
1 1 723.4 nA
0 0 0 mA
C.2 Analog value display with failure monitoring in the current
measurement range 4...20 mA (4...20 mA HART)
Table C-2 Representation / current measuring range with failure monitoring according to NE43
(current measuring range 4 to 20 mA and 4 to 20 mA HART)
Values NE43
hex mA Ranges QI Interrupt
Overow range
(upper failure range)
7FFF bad Overow
7EFF 22.81
72C0 21
Hysteresis
1)
6F60 20.5
Measuring range Process val‐
ues
good
6C00 20
0 4
FFFF 3.9994
FEA6 3.8 Hysteresis
2)
AI 4xI 2-/4-wire HART ISOL HA
Equipment Manual, 07/2022, A5E50101523-AB 85