Parameter Value range Default Parameter reas‐
signment in
RUN
Eciency range
High limit 1/2 (Page 29) Value 20 mA Yes Channel
Low limit 1 / 2 (Page 29) Value 4 mA at 4 to 20 mA
1 μA at 0 mA to
20 mA
Yes Channel
5.4 Explanation of the module/channel parameters
5.4.1 Diagnostics, Missing supply voltage L+
Denition
Enabling of the diagnostics for missing or insucient supply voltage L+.
5.4.2 IO redundancy
Denition
You can congure two identical modules redundantly. To do so, plug both modules into a
redundant terminal block side by side. You can nd additional information on mounting
modules in an IO redundancy conguration in the ET 200SP HA System Manual, section
"Installing", "Installing terminal block".
In IO redundancy mode, the left module is the master and the right module is the slave. The
HART communication takes place exclusively via one of the two redundant channels.
Description
The acquired process value is made available on both the modules in error-free, redundant
operation.
When IO redundancy operates without error, HART communication takes place exclusively via
one of the two redundant channels. The HART interface of all channels is associated with the
master by default. If a module fails or a channel failure is detected, the HART interface of the
aected channels changes to the partner module. Once an error has been corrected, there is no
changeover of the HART interface of the current-carrying channels involved.
Parameters
5.4 Explanation of the module/channel parameters
AI 4xI 2-/4-wire HART ISOL HA
24 Equipment Manual, 07/2022, A5E50101523-AB