B.4 HART feature data
Structure of the HART feature data
Byte Meaning Comment
0 Byte 0 = 0x62
Bit 1 = 1: "Parameter check result is given with a read response"
Bit 5 = 1: "Compact format is supported"
Bit 6 = 1: "SHC mode is supported"
1 Byte 1 = 0
2 Max Length Da‐
ta Unit
= 230 (maximum length of the HART request data records)
B.5 HART variable data record
The I/O module supports a maximum of 4 HART variables per channel when HART mode is
enabled. Provided they are supported by the connected 󹪝eld device, these variables are ready
cyclically.
The total of 16 HART variables are made available in HART variable data record 121 as readable
variables.
Each HART variable consists of a 4-byte real value and 1-byte quality code.
In IO redundancy mode, the HART variables are only updated if the HART interface is on the
corresponding module/channel. The channel may not be in standby mode. If the HART interface
is on the partner module/partner channel, the corresponding HART variable is initialized (quality
code = 0x37).
Structure of the HART variable data record
Byte Meaning
Channel 0
0…3 Value Primary Variable (PV)
4 Quality Code
5…8 Value Secondary Variable (SV)
9 Quality Code
10…13 Value Tertiary Variable (TV)
14 Quality Code
15…18 Value Quaternary Variable (QV)
19 Quality Code
Channel 1
20…39 HART variables same as for channel 0
Channel 2
40…59 HART variables same as for channel 0
HART operating data records
B.5 HART variable data record
AI 4xI 2-/4-wire HART ISOL HA
Equipment Manual, 07/2022, A5E50101523-AB 81