Loading...
Diagnostics mes‐
sage
Error
code
Assignment Meaning Remedy
Retentive memo‐
ry in carrier mod‐
ule defective
154
H
Module A memory block error was detected on the
support module
Replace carrier module
Retentive memo‐
ry in the terminal
block defective
155
H
Module A memory block error was detected on the
terminal block
Replace terminal block
1
Only the terminal blocks (TB 45R ...) are suitable for use with I/O modules in IO redundancy.
A.5 Maintenance events
Maintenance events
A maintenance event is generated each time a maintenance requirement is identi󹪝ed. The MT
LED lights up on the module.
Maintenance messages are assigned either to one input on a channel-speci󹪝c basis (HART error)
or to inputs as a module message a󹪜ecting all inputs.
Maintenance messages have no direct e󹪜ect on the function of the module or the analog value
acquisition. Maintenance events of the HART communication do not a󹪜ect the analog value
acquisition of the module.
Table A-2 Maintenance messages, their meaning and possible remedies
Maintenance
message
Error
code
Assignment Meaning / Cause Remedy
Redundancy part‐
ner has di󹪜erent
hardware/󹪝rm‐
ware version
120
H
Module The redundantly con󹪝gured and intercon‐
nected I/O modules are not compatible
Check and replace modules
IO redundancy
warning
121
H
Module Unable to correctly communicate with the
partner module
Check/replace right module
Check/replace left module
Check/replace terminal
block
See also system manual Distrib‐
uted I/O System; ET 200SP HA",
section "Replacing an I/O mod‐
ule for I/O redundancy"
HART communica‐
tion error
141
H
Analog input
HART 󹪝eld device is not responding
Timing error
HART 󹪝eld device did not understand the
command that was sent (1st status byte)
Check the process wiring
Correct the parameter as‐
signment
Set current ≥4 mA
Increase number of con󹪝g‐
ured repetitions
Parameters, diagnostics messages and address space
A.5 Maintenance events
AI 4xI 2-/4-wire HART ISOL HA
Equipment Manual, 07/2022, A5E50101523-AB 65