3.3 Setting the PROFIBUS DP address
Interface module IM 155-6 DP HF (6ES7155-6BA01-0CN0)
20 Manual, 10/2018, A5E03916550-AD
3.3
Setting the PROFIBUS DP address
Introduction
On the interface module (PROFIBUS), set the PROFIBUS DP address for PROFIBUS DP
using the DIP switch. By setting the PROFIBUS DP address, you specify where the
ET 200SP is to be addressed on the PROFIBUS DP.
Requirements
Each PROFIBUS DP address may be assigned only once on the PROFIBUS DP.
Valid PROFIBUS DP addresses are 1 to 125.
The set PROFIBUS DP address must match the PROFIBUS DP address specified for the
ET 200SP in the configuration software.
Required tools
Screwdriver 3 - 3.5 mm
Setting the PROFIBUS DP address
1. Slide the window of the interface module upwards.
2. Use a screwdriver to set the required PROFIBUS address via the DIP switch.
3. Close the window.
Figure 3-2 Setting the PROFIBUS DP address
Changing the PROFIBUS DP address
You can change the PROFIBUS DP address in exactly the same way as you set it.
A change
in the PROFIBUS DP address only becomes valid for the ET 200SP
after a POWER ON of
the interface module
.