Interrupts, error messages, diagnostics and system alarms
5.1 Status and error displays
Interface module IM 155-6 DP HF (6ES7155-6BA01-0CN0)
26 Manual, 10/2018, A5E03916550-AD
RN/ER/MT LEDs on the interface module
Table 5- 1 Status and error displays of RN/ER/MT LEDs
No or too little supply voltage at inter-
face module
Check the supply voltage or switch it
on at the interface module.
1
On
On
On
Test of LEDs during startup: The three
LEDs light up simultaneously for ap-
-
Flashes
Off
Off
Interface module is deactivated. Activate the interface module with the
configuration software or the user
Interface module is not configured. Configure the interface module with
the configuration software.
-
ET 200SP is being assigned parame-
Not relevant Not relevant ET 200SP is currently exchanging
data with the DP master.
-
Not relevant
Flashes
Not relevant Group error and group error channels Evaluate the diagnostics and eliminate
The preset configuration does not
match the actual configuration of the
ET 200SP.
Check the configuration of the
ET 200SP to see whether a module is
missing or faulty, or whether a non-
configured module is inserted.
Invalid configuration states See the Invalid configuration states of
the ET 200SP on PROFINET DP
Parameter assignment error in the I/O
module
Evaluate the display of the module
status in STEP 7 and correct the error
in the corresponding I/O module.
Not relevant Not relevant
On
Maintenance is demanded. Perform maintenance
Flashes
Flashes
Flashes
Hardware or firmware faulty.
2
Run a firmware update. If the error
persists, contact Siemens Industry
Online Support.
Replace the interface module.
PWR LED On (on interface module): Check the backplane bus for a short-circuit.