EasyManua.ls Logo

Siemens SIMATIC FM 353 - Page 311

Siemens SIMATIC FM 353
361 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Troubleshooting
11-9
FM 353 Stepper Drive Positioning Module
6ES7 353-1AH01-8BG0
11.3 Error lists
Note
In the following tables, please note:
The module response described under “Effect” refers to the error-specific module
response. The error response described in Table 11-2 occurs in addition.
11.3.1 Diagnostic interrupts
Overview
The diagnostic interrupts are listed according to error class in Tables 11-4, 11-5.
Table 11-4 Diagnostic interrupt
Byte.
Bit
Error message,
error analysis and remedy
Message/
Display
0.1 Internal errors Error response: “Everything Off”, as in Table 11-2
2.1
(8031)
Communication disturbance
SF
(8031)
Cause MPI/K-bus communication fault caused by unknown event
SF
DC5V
DIAG
Effect MPI interface inactive
DIAG
Elimination S Check connection
S Check programming device/CPU
S Switch module on/off
S Replace module
2.3
(8033)
Internal time monitoring circuit (Watchdog)
(8033)
Cause S Pronounced noise conditions on the FM 353
S Errors in the FM 353
Effect S Deactivate entire FM 353
S LED indicators:
DIAG: Flashing cycle
SF: ON
Elimination S If this manual is observed, the errors should not occur
However, should this still be the case, please consult the re-
sponsible sales department. When doing so, it is vitally impor-
tant to also report the exact circumstances leading to the error.
S Replace the FM 353
Note: (xxxx) value = Hexadecimal notation in diagnostic buffer

Table of Contents