Installing and connecting the device
3.3 Connecting the device
SIMATIC IPC527G
28 Operating Instructions, 03/2019, A5E45491226-AA
WARNING
Electric shock and risk of fire
High voltage may be present in a defective device, which can cause fire or an electric
shock if touched. Death and serious bodily injury can result.
Connect the device to the function earth before you put it into operation.
The function earth terminal on the device must be connected to the function earth of the
control cabinet or system in which the device is installed.
Never operate the device without function earth.
If a device is defective, remove it from operation without delay and label it accordingly.
Requirement
T20 screwdriver
Cable lug for M4
Function earth with minimum cross-section of 2.5 mm
2
copper cable
Procedure
Clamp the cable lug on the function earth.
Firmly attach the cable lug to the function earth conne
c
tion on
the device using the M4 thread (see part label
ed).
Connect the function earth to the protective conductor
connection of the cabinet or the plant in which the device is
i
nstalled.