EasyManuals Logo

Siemens Simatic S7-1500 CPU 1512C-1 PN User Manual

Siemens Simatic S7-1500 CPU 1512C-1 PN
206 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #111 background imageLoading...
Page #111 background image
Wiring
4.3 Terminal and block diagrams
CPU 1512C-1 PN (6ES7512-1CK01-0AB0)
Manual, 12/2017, A5E40898741-AA
111
4.3.8
Interconnection overview of outputs
Combined interconnection of the technology channels
The following table provides you with an overview of the possible interconnections of the
front connectors X11 and X12 to allow you to correctly divide the available inputs between
the possible technology channels HSC, PWM and PTO. This overview is a combination of
interconnection options of technology channels for HSC, PWM and PTO.
Hardware output
Standard DQ
PWM
PTO
HSC
Front
con-
nect-
or
Ter
min
al
Cha
nnel
Output module
Configurable
as standard
DQ for channel
Configurable
as PWM output
for channel
Configurable
as PTO output
A for chan-
nel
1)
Configurable
as PTO output
B for chan-
nel
2)
Configura-
ble as
"Drive
enable
output" for
channel
Can be used
as HSC-DQ1
for channel
X11 1 DQ
0
High-speed
PWM1
PTO1
Standard
DQ0
PWM1
[PTO 2/3/4]
2 DQ
1
High-speed
PTO1
[HSC1]
Standard DQ1 [PTO
1/2/3/4]
3 DQ
2
High-speed
PWM2
PTO2
Standard
DQ2
PWM2
[PTO 1/3/4]
4 DQ
3
High-speed
PTO2
HSC2
Standard DQ3 [PTO
1/2/3/4]
5 DQ
4
High-speed
PWM3
PTO3
[HSC3]
Standard
DQ4
PWM3
[PTO 1/2/4]
6 DQ
5
High-speed
PTO3
[HSC4]
Standard DQ5 [PTO
1/2/3/4]
7 DQ
6
High-speed
PWM4
PTO4
HSC6
Standard
DQ6
PWM4
[PTO 1/2/3]
8 DQ
7
High-speed
PTO4
[HSC5]
Standard DQ7 [PTO
1/2/3/4]
11 DQ
8
Standard
DQ8 PWM1 [PTO
1/2/3/4]
12 DQ
9
DQ9 PTO1
*
[PTO
1/2/3/4]
[HSC1]
13 DQ
10
DQ10 PWM2 [PTO
1/2/3/4]
14 DQ
11
DQ11 PTO2
*
[PTO
1/2/3/4]
HSC2
15 DQ
12
DQ12 PWM3 [PTO
1/2/3/4]
[HSC3]
16 DQ
13
DQ13 PTO3
*
[PTO
1/2/3/4]
[HSC4]
17 DQ
14
DQ14 PWM4 [PTO
1/2/3/4]
HSC6
18 DQ
15
DQ15 PTO4
*
[PTO
1/2/3/4]
[HSC5]

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens Simatic S7-1500 CPU 1512C-1 PN and is the answer not in the manual?

Siemens Simatic S7-1500 CPU 1512C-1 PN Specifications

General IconGeneral
Integrated InterfacesPROFINET
Data Memory1 MB
Number of Signal Boards1
Firmware VersionV2.8
Rated Value (DC)24 V
Number of PROFINET Ports2
Number of PROFINET Ports with Switch2
Integrated Web ServerYes
Number of Digital Inputs16
Number of Digital Outputs16
Number of Analog Outputs2
Number of High-speed Counters6
Program Memory300 KB
Number of Signal Modules32
Engineering withSTEP 7 Professional V13
Interface TypeEthernet
Data StorageYes
Operating Temperature0 to 60 °C
Dimensions147 mm x 129 mm