EasyManuals Logo

Siemens Simatic S7-1500 CPU 1512C-1 PN User Manual

Siemens Simatic S7-1500 CPU 1512C-1 PN
206 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #175 background imageLoading...
Page #175 background image
Parameter data records
B.4 Parameter assignment and structure of the parameter data records of the digital on-board I/O
CPU 1512C-1 PN (6ES7512-1CK01-0AB0)
Manual, 12/2017, A5E40898741-AA
175
B.4
Parameter assignment and structure of the parameter data records
of the digital on-board I/O
Parameter assignment in the user program
You have the option of reassigning parameters for the digital on-board I/O in RUN (for
example, values for input delay of individual channels can be modified in RUN without
affecting the other channels).
Changing parameters in RUN
The parameters are transferred to the digital on-board I/O via data records 0 to 15 with the
WRREC instruction. The parameters set with STEP 7 (TIA Portal) are not changed in the
CPU, which means the parameters set in STEP 7 (TIA Portal) will be valid again after a
restart.
The parameters are only checked for plausibility after the transfer.
Output parameter STATUS
If errors occur when transferring parameters with the "WRREC" instruction, the digital on-
board I/O continues operation with the previous parameter assignment. However, a
corresponding error code is written to the STATUS output parameter.
You will find a description of the "WRREC" instruction and the error codes in the STEP 7
(TIA Portal) online help.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens Simatic S7-1500 CPU 1512C-1 PN and is the answer not in the manual?

Siemens Simatic S7-1500 CPU 1512C-1 PN Specifications

General IconGeneral
Integrated InterfacesPROFINET
Data Memory1 MB
Number of Signal Boards1
Firmware VersionV2.8
Rated Value (DC)24 V
Number of PROFINET Ports2
Number of PROFINET Ports with Switch2
Integrated Web ServerYes
Number of Digital Inputs16
Number of Digital Outputs16
Number of Analog Outputs2
Number of High-speed Counters6
Program Memory300 KB
Number of Signal Modules32
Engineering withSTEP 7 Professional V13
Interface TypeEthernet
Data StorageYes
Operating Temperature0 to 60 °C
Dimensions147 mm x 129 mm

Related product manuals