EasyManua.ls Logo

Siemens Simatic S7-1500 CPU 1512C-1 PN - Structure of a Data Record for Output Channels of the Analog On-Board I;O

Siemens Simatic S7-1500 CPU 1512C-1 PN
206 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Parameter data records
B.3 Structure of a data record for output channels of the analog on-board I/O
CPU 1512C-1 PN (6ES7512-1CK01-0AB0)
172 Manual, 12/2017, A5E40898741-AA
B.3
Structure of a data record for output channels of the analog on-
board I/O
Assignment of data record and channel
The parameters for the 2 analog output channels are located in data records 64 and 65 and
are assigned as follows:
Data record 64 for channel 0
Data record 65 for channel 1
Data record structure
The figure below shows the structure of data record 64 for channel 0 as an example. The
structure is identical for channel 1. The values in byte 0 and byte 1 are fixed and must not be
changed.
You enable a parameter by setting the corresponding bit to "1".