EasyManua.ls Logo

Siemens Simatic S7-1500 CPU 1512C-1 PN - Page 154

Siemens Simatic S7-1500 CPU 1512C-1 PN
206 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Technical specifications
CPU 1512C-1 PN (6ES7512-1CK01-0AB0)
154 Manual, 12/2017, A5E40898741-AA
Article number
6ES7512-1CK01-0AB0
Update time for IRT
for send cycle of 250 µs
250 μs to 4 ms; Note: In the case of IRT with
isochronous mode, the minimum update time of
625 µs of the isochronous OB is decisive
for send cycle of 500 µs
500 μs to 8 ms; Note: In the case of IRT with
isochronous mode, the minimum update time of
625 µs of the isochronous OB is decisive
for send cycle of 1 ms
1 ms to 16 ms
for send cycle of 2 ms
2 ms to 32 ms
for send cycle of 4 ms
4 ms to 64 ms
With IRT and parameterization of "odd"
send cycles
Update time = set "odd" send clock (any multiple
of 125 µs: 375 µs, 625 µs ... 3 875 µs)
Update time for RT
for send cycle of 250 µs
250 µs to 128 ms
for send cycle of 500 µs
500 µs to 256 ms
for send cycle of 1 ms
1 ms to 512 ms
for send cycle of 2 ms
2 ms to 512 ms
for send cycle of 4 ms
4 ms to 512 ms
PROFINET IO Device
Services
PG/OP communication
Yes
S7 routing
Yes
Isochronous mode
No
Open IE communication
Yes
IRT
Yes
MRP
Yes
MRPD
Yes; Requirement: IRT
PROFIenergy
Yes
Shared device
Yes
Number of IO Controllers with shared
device, max.
4
Asset management record
Yes; Per user program
Interface types
RJ 45 (Ethernet)
100 Mbps
Yes
Autonegotiation
Yes
Autocrossing
Yes
Industrial Ethernet status LED
Yes