Commissioning 
  8.5 Commissioning PROFIBUS DP 
S7-300, CPU 31xC and CPU 31x: Installation 
Operating Instructions, Edition 08/2004, A5E00105492-05 
8-33 
PROFIBUS address 
For the DP CPU, you must not set "126" as a PROFIBUS address. 
See also 
Consistent data (Page 7-8) 
User-specific addressing of modules (Page 7-3) 
8.5.4  Direct data exchange 
Requirements 
STEP 7 V 5.x or higher lets you configure "Direct data exchange" for PROFIBUS nodes. DP 
CPUs can take part in direct data exchange as senders and receivers. 
Definition 
"Direct data exchange" is a special communication relationship between PROFIBUS DP 
nodes. 
Characteristic of direct data exchange are the PROFIBUS DP nodes "Listening" on the bus 
for data a DP slave returns to its DP master. This mechanism allows "Listening stations" 
(receivers) direct access to modified input data of remote DP slaves. 
Address Areas 
In your STEP 7 configuration of the relevant peripheral input addresses, specify which 
address area of the receiving node is to receive data requested from the sending node. 
The following types of DP-CPU are possible: 
•  DP slave sending station 
•  Receiving station, as DP slave or DP master, or as CPU not integrated in a master 
system.