Configuring 
  4.9 Electrical assembly, protective measures and grounding 
S7-300, CPU 31xC and CPU 31x: Installation 
Operating Instructions, Edition 08/2004, A5E00105492-05 
4-15 
Result 
The figure below shows the resultant ambient temperatures, based on an accumulated 
power loss of 650 W: 
Table 4-6  Cabinet selection 
Cabinet design  Maximum permitted ambient 
temperature 
Closed with natural convection and forced convection (trend 
3) 
Operation not possible 
Open with through-ventilation (trend 2)  approx. 38 °C 
Closed with heat exchanger (trend 1)  approx. 45 °C 
Cabinet types suitable for horizontal installation of the S7-300: 
•  open, with closed ventilation 
•  closed, with heat exchanger 
4.9  Electrical assembly, protective measures and grounding 
4.9.1  Grounding concept and overall structure 
This section contains information about the overall configuration of an S7-300 connected to a 
grounded TN-S network: 
•  Circuit-breaking devices, short-circuit and overload protection to VDE 0100 and VDE 
0113 
•  Load power supplies and load circuits 
•  Grounding concept 
 
 
 
Note 
An S7-300 can be used in many different ways, so we can only describe the basic rules 
for the electrical installation in this document. Those basic rules are a must in order to 
achieve a fully functional S7-300 system. 
 
Definition: Grounded mains 
In a grounded mains network, the neutral conductor is always bonded to ground. A short-
circuit to ground of a live conductor, or of a grounded part of the system, trips the protective 
devices.