A.2 Protection against electromagnetic interference 
  S7-300, CPU 31xC and CPU 31x: Installation 
A-6  Operating Instructions, Edition 08/2004, A5E00105492-05 
A.2.2.3  3. Basic rule for ensuring EMC 
Rule 3: Fixing the cable shielding 
Ensure proper fixation of the cable shielding. 
•  Always use shielded data cable. Always connect both ends of the shielding to ground on 
a large area. 
•  Analog cables must always be shielded. For the transmission of low-amplitude signals it 
might prove to be more efficient to have only one side of the shielding connected to 
ground. 
•  Directly behind the cable entry in the cabinet or enclosure, terminate the shielding on a 
large area of the shielding/protective ground bar and fasten it with the help of a cable 
clamp. Then, route the cable to the module; however, do not connect the shielding once 
again to ground in this place. 
•  Connections between the shielding/protective ground conductor bar and the 
cabinet/enclosure must be of a low impedance. 
•  Always install shielded data cables in metal/metallized connector housings. 
See also 
Cable shielding (Page A-12) 
A.2.2.4  4. Basic rule for ensuring EMC 
Rule 4: Special EMC measures 
Take special EMC measures for particular applications. 
•  Connect anti-surge elements to all inductive devices not controlled by S7-300 modules. 
•  For cabinet or cubicle lighting in the immediate range of your controller, use incandescent 
lamps or interference suppressed fluorescent lamps. 
See also 
How to protect digital output modules against inductive surge voltage (Page A-28)