4.9 Electrical assembly, protective measures and grounding 
  S7-300, CPU 31xC and CPU 31x: Installation 
4-16  Operating Instructions, Edition 08/2004, A5E00105492-05 
Specified components and protective measures 
A number of components and protective measures are prescribed for plant installations. The 
type of components and the degree of compulsion pertaining to the protective measures will 
depend on the VDE specification applicable to your particular plant.  
The table below shows components and protective measures.  
Table 4-7  VDE specifications for the installation of a PLC system 
Compare ...  1)  VDE 0100  VDE 0113 
Disconnect devices for control 
systems, signal generators and 
final control elements 
 (1)  ...Part 460:  
Master switch 
... Part 1: 
Load disconnect switch 
Short-circuit / overload 
protection: 
In groups for signal generators 
and final control elements 
 (2)  ...Part 725: 
Single-pole fusing of 
circuits 
... Part 1: 
•  With grounded secondary 
power circuit: single-pole 
fusing 
•  Otherwise: fusing of all poles 
Load power supply for AC load 
circuits with more than five 
electromagnetic devices 
 (3)  Galvanic isolation by 
transformer 
recommended 
Electrical isolation by transformer 
mandatory 
 1) This column refers to the indexes of the figure in the chapter Overview: Grounding. 
Reference 
For further information on protective measures, refer to the Appendix. 
4.9.2  Installing an S7-300 with grounded reference potential 
Introduction 
During installation of an S7-300 with grounded reference potential interference current is 
discharged to the ground conductor / to earth. A grounding slide contact is used for this 
except with CPU 31xC. 
 
 
Note 
Your CPU is supplied with grounded reference potential. Therefore, if you wish to install an 
S7-300 with grounded reference potential, you do not need to modify your CPU!