Configuring   
4.9 Electrical assembly, protective measures and grounding 
  S7-300, CPU 31xC and CPU 31x: Installation 
4-22  Operating Instructions, Edition 08/2004, A5E00105492-05 
Measures for protective grounding 
The table below shows an overview of the most important measures for protective 
grounding. 
Table 4-8  Measures for protective grounding 
Device  Measures 
Cabinet / mounting frame  Connection to central ground (equipotential busbar, for example) 
using cables with protective conductor quality 
Rack / mounting rail  Connection to central ground, using cables with a minimum cross-
section of 10 mm
2
, if the rails are not installed in the cabinet and not 
interconnected with larger metallic parts. 
Module  None 
I/O Device  Grounding via grounding-type plug 
Sensors and final control 
elements 
Grounding in accordance with regulations applying to the system 
Rule: Connect the cable shielding to ground 
You should always connect both ends of the cable shielding to ground / system ground. This 
is the only way to achieve an effective interference suppression in the higher frequency 
range. 
Attenuation is restricted to the lower frequency range if you connect only one end of the 
shielding (that is, at the start or end of the cable) to ground. One-sided shielding connections 
could be more favorable in situations 
•  not allowing the installation of an equipotential bonding conductor, 
•  where analog signals (some mA or A) are transferred, 
•  or if foil shielding is used (static shielding). 
 
 
 
Note 
Potential differences between two grounding points might cause an equipotential current 
flow across shielding connected at both ends. In this case, you should install an 
additional equipotential bonding conductor. 
 
 
 
 
Caution 
Always avoid the flow of operating current to ground.