Appendix
A.2 Protection against electromagnetic interference
S7-300, CPU 31xC and CPU 31x: Installation
A-8 Operating Instructions, Edition 08/2004, A5E00105492-05
Observe the following for ground connection:
In the same way as with active elements, exercise meticulous care to interconnect
inactive metal elements.
Always make sure that you have a low-impedance interconnection between metal
elements (e.g. large and highly conductive contact surface).
The protective insulating finish on varnished or anodized metal elements must be pierced
or removed. Use special contact washers or completely remove the finish on the point of
contact.
Protect your connecting elements against corrosion (e.g. with a suitable grease).
Interconnect moving chassis ground elements (e.g. cabinet doors) with flexible ground
straps. Always use short ground straps with a large surface (the surface is decisive for
the diversion of high-frequency currents).