Information for the Changeover to the Technology CPU
9.12 Information about interface X3 DP(DRIVE)
No diagnosis on DP(DRIVE)
Remember that you cannot evaluate diagnostic data from DP(DRIVE) in your STEP 7 user
program if you are using the Technology CPU.
However, with your PC/PG connected to PROFIBUS DP, you can use the "routing" function
to access drive parameters in the DP(DRIVE) line (in conjunction with appropriate drive
tools) for commissioning and diagnostic purposes.
S7-300 CPU Data: CPU 315T-2 DP
9-8 Manual, 12/2005, A5E00427933-02

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIMATIC S7-300 CPU Data: CPU 315-T-2 DP and is the answer not in the manual?

Siemens SIMATIC S7-300 CPU Data: CPU 315-T-2 DP Specifications

General IconGeneral
Programming LanguageSTEP 7
Power Supply24 V DC
Number of DP masters1
Processable Technology objectsYes
Number of counters256
Number of timers256
S7 communicationYes
Number of connections for S7 communication, max.16
PG/OP communicationYes
Global data communicationYes
Integrated DP interfaceYes
Integrated PROFINET interfaceNo
SIMATIC Computing PlatformNo
Operating Temperature0 to 60 °C
Integrated InterfacesMPI, DP
CommunicationPROFIBUS DP
Cycle Time0.1 ms
Engineering withSTEP 7
Backup availableYes
Transmission rate, max.12 Mbit/s