Memory concept
6.1 Memory areas and retentive address areas
The diagnostics buffer, MPI address (and transmission rate) and operating hour counter data
are generally written to the retentive memory area on the CPU. The retentive address areas
of the MPI address and transmission rate ensures that your CPU can continue to
communicate, even after a power loss, memory reset or loss of communication parameters
(e.g. due to removal of the MMC or deletion of communication parameters).
Working memory
The retentive data in the working memory are saved to a non-volatile memory on the CPU
during POWER OFF. Therefore, contents of retentive DBs are always retentive.
With the Technology CPU, non-retentive DBs are also supported (the non-retentive DBs are
initialized at restart and POWER OFF-ON with their initial values from the load memory).
Technology system data
The technology system data are always stored as retentive data in the load memory of the
CPU.
6.1.3 Retentive behavior of the memory objects
Retentive behavior of the memory objects
The table below shows the retentive behavior of memory objects during specific operating
state transitions.
Table 6-1 Retentive behavior of the memory objects
Memory object Operating state transition
POWER ON /
POWER OFF
STOP →
RUN
CPU memory
reset
User program/data (load memory) X X X
Can be set in the Properties of the
DBs.
-
Retentive behavior of the DBs (without
technology DB)
Retentive behavior of the technology
DBs
- - -
Flags, timers and counters configured as
retentive data
X X -
Diagnostics buffer, operating hour counters X X X
MPI/DP address, transmission rate
(or also DP address, transmission rate of
the Technology CPU MPI/DPinterface, if
this is parameterized as DP node).
X X X
Technological parameters
Changed with FB "MC_WriteParameter"
Changed with
S7TConfig
-
X
X
X
-
X
x = retentive; - = non-retentive
S7-300 CPU Data: CPU 315T-2 DP
Manual, 12/2005, A5E00427933-02
6-3

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIMATIC S7-300 CPU Data: CPU 315-T-2 DP and is the answer not in the manual?

Siemens SIMATIC S7-300 CPU Data: CPU 315-T-2 DP Specifications

General IconGeneral
Programming LanguageSTEP 7
Power Supply24 V DC
Number of DP masters1
Processable Technology objectsYes
Number of counters256
Number of timers256
S7 communicationYes
Number of connections for S7 communication, max.16
PG/OP communicationYes
Global data communicationYes
Integrated DP interfaceYes
Integrated PROFINET interfaceNo
SIMATIC Computing PlatformNo
Operating Temperature0 to 60 °C
Integrated InterfacesMPI, DP
CommunicationPROFIBUS DP
Cycle Time0.1 ms
Engineering withSTEP 7
Backup availableYes
Transmission rate, max.12 Mbit/s

Related product manuals